DP Transmitter to Flow Square Root Calculator

Professional DP ↔ Flow Engineering Calculator
F = C × √ΔP
📋 1. Document Information
⚙️ 2. Calculation Input
Enter the measured differential pressure value
Lower Range Value
Upper Range Value = ΔP maximum
C = Fmax / √ΔPmax (auto-calculated)
ΔP = P1 − P2 (informational)
📊 3. Calculation Results
Calculated ΔP
—
Calculated Flow
—
Flow Coefficient C
—
ΔP Ratio (% of Max)
—
Flow (% of Max)
—
Flow at ΔP LRV
—
Flow Span
—
Inverse Check
—
📈 4. DP vs Flow Correlation
ΔP % ΔP Value Flow Value Flow %
✅ 5. Reference Example Verification
Example Given Expected Calculated Status
1 ΔPmax=2500 mmH₂O, Fmax=6000 m³/h, ΔP=500 mmH₂O → F=? ≈ 2,683.28 m³/h — —
2 ΔPmax=2500 mmH₂O, Fmax=6000 m³/h, F=3500 m³/h → ΔP=? ≈ 850.69 mmH₂O — —
✍️ 6. Execution & Approval
Role Name Signature Date
Prepared By——
Checked By——
Approved By——